See the picture below, if it is same with yours, that means the THC can’t receive the arc signal or receive the wrong arc signal, please check as below:
- 1. Check if you connect the DIV ARC+&DIV ARC- in wrong direction, so you can exchange the two wires to test, if this doesn’t work, see the step 2.
- 2. Do you connect the raw arc voltage signal to DIV ARC+&DIV ARC-? It should be between 50v-300v, some plasma give out divided arc voltage, if you connect this to our machine, the THC maybe stay.
- 3. If the two steps above can’t resolve your problem, you should test if the terminals which you connect the DIV ARC+&DIV ARC- are right. The terminal which you connect to the DIV ARC+ should be conductive with the electrode, and the terminal which you connect to the DIV ARC- should be conductive with the metal plate that you want to cut, you can use a multimeter to test, if not thus, please check if you connect to the wrong terminals.